Incorporates a 20 foot long, vapor charged, sensing element. Reacts to the coldest 18 inch section of the controls sensing element. Suitable for monitoring the face temperature of hot water coils for freeze protection. SINGLE STAGE TEMPERATURE CONTROLS 392 Part numbers and illustrations are for identification only © 1971 - 2010 w.d. armstrong corp. LOW TEMPERATURE CUTOUT CONTROL REMOTE BULB CONTROLS Features • snap-acting switch • external temperature scale • easy setpoint adjustment with top or bottom access Applications • low temp. cut-out for coils and/or pipe liquid sensing Specifications •   ambient temperature of control: 0-140°F (-17.8 -60°C) •  maximum element temperature: 250°F (121°C) Part No. Switch Range Differential Bulb & Capillary A11A-1C Manual Reset A11B-1C 8°F (4.4°C) (Fixed) SPST Open Low 35 to 45°F 2 to 7°C 20 ft. of 1/8” O.D. Tubing 4’ Cap. Suitable for temperature control in heating, ventilating, and refrigeration. Single stage temperature controls that incorporate liquid filled sensing elements. Features • wide temperature ranges available • constant differential throughout the entire range • compact enclosure • fixed or adjustable differential available • variety of sensing element styles • unaffected by cross-ambient conditions Accessories A packing nut is available for closed tank application. Specify the part number FTG13A-600R. Bulb wells (WEL14A Series) are available for liquid immersion applications. Bulb Max Switch Well No. Bulb Part No. Action Range Diff Bulb Cap. WELL14A-   Temp Adjustable Differential (Wide Range) A19ABA-40C1  SPST -30 to 100ºF 3 to12ºF 3/8” x 4” 6’ 602R 140ºF Open Low -34 to 38ºC 1.7 to 6.7°C 60ºC A19ABC-4C SPDT 50 to 130ºF 3.5 to14ºF 3/8” x 4” 8’ 603R 170ºF 10 to 55ºC 1.9 to 8ºC 77ºC Fixed Differential (Case Compensated) A19AAF-12C SPDT 25 to 225ºF 3.5ºF 3/8” x 3” 10’ 602R 140ºF -4 to 107ºC 1.9ºC 60ºC Manual Reset A19ADB-1C SPST 100 to 240ºF - 3/8” x 3½” 6’ 602R 290ºF Open High 38 to 116ºC - 143ºC 1.  Replaces: White-Rodgers 1609-101